Step by step
- List each 24 V load and its current: PLC and I/O, sensors, relays and contactor coils, HMI, valves, drives' control supply.
- Add the currents to get the continuous load.
- Allow for inrush and peaks: contactors, solenoid valves and capacitive loads draw more when switching on.
- Add 20 to 30 percent headroom so the supply is not running at its limit.
- Choose a standard supply rating at or above that figure (for example 5 A, 10 A or 20 A).
- Check derating: many supplies lose output at high ambient temperature, so confirm the rating at your cabinet temperature.
Protection and layout
- Use electronic circuit breakers or fuses for each branch so one fault does not take down the whole machine.
- Keep sensitive 24 V circuits separate from relay and valve circuits where possible.
- Leave clearance around the supply for cooling.
Redundancy
For critical machines, use two supplies with a redundancy module so one can fail without stopping production. Size each supply to carry the full load alone.
Frequently asked questions
How much headroom should a power supply have?
A margin of 20 to 30 percent is common. It lowers heat, extends life and covers load added later.
What is inrush current?
It is the brief higher current drawn when a load switches on, for example a capacitor or a solenoid. The supply must handle it without tripping.
Do I need a redundancy module?
Only when losing 24 V would cause a stop you cannot accept. Many machines run on a single supply.
This guide is general engineering guidance. Always confirm part-specific details, ratings and compatibility against the manufacturer’s datasheet. We confirm price, stock and specifications for the exact part in a written quotation.